E658130
- 9 -
4.4. The maximum connection number of units
1. Maximum number of units connected to one master station (CC-Link Ver.1.10)
42 units (when only inverters are connected)
If any other units are included, the number of stations occupied depends on the unit and
therefore the following conditions must be satisfied:
{(1 × a) + (2 × b) + (3 × c) + (4 × d)} 64
a: Number of units occupying 1 station
b: Number of units occupying 2 stations
c: Number of units occupying 3 stations
d: Number of units occupying 4 stations
{(16 × A) + (54 × B) + (88 × C)} 2304
A: Number of remote I/O stations 64
B: Number of remote device stations 42
C: Number of local, standby master and intelligent device stations 26