TOSVERT VF-S15 series
®
option unit Function Manual
CCL003Z
NOTICE
1. Read this manual before installing or operating. Keep this instruction manual on
hand of the end user, and make use of this manual in maintenance and inspection.
2. All information contained in this manual will be changed without notice. Please
contact your Toshiba distributor to confirm the latest information.
Zobrazit stránku 0
1 2 3 4 5 6 ... 50 51

Shrnutí obsahu

Strany 1 - option unit Function Manual

E6581830 TOSVERT VF-S15 series ® option unit Function Manual CCL003Z NOTICE 1. Read this manual before

Strany 2 - Introduction

E658130 - 9 - 4.4. The maximum connection number of units 1. Maximum number of units connected to one master station (CC-Link Ver.1.10) 42 units (w

Strany 3 - Caution

E658130 - 10 - 2. Maximum number of units connected to one master station (CC-Link Ver.2.00) 42 units (when connections are inverter only) If any ot

Strany 4 - Table of Contents

E658130 - 11 - 4.5. LED indicator The LEDs shows the present status of the network and module Refer to 7.3 for detail. Layout of LED L.R

Strany 5 - 2. Basic specifications

E658130 - 12 - 5. Functions This option is a communication interface unit that allows the PLC program to operate, monitor and set the parameter o

Strany 6 - 2.1.2. CC-Link Ver. 2

E658130 - 13 - 5.2. Communication parameters for CCL003Z Title Function Description c100 Communication error detection delay time 0.0 - 100.0

Strany 7 - 3. Names and functions

E658130 - 14 - 5.3. CC-Link function setting 5.3.1. Station number setting Use parameter c120 to set station number of the inverter. Set this para

Strany 8 - 4. Installation on inverter

E658130 - 15 - 5.3.3. CC-Link extended setting Remote register function can be extended. Title Function Description c122* CC-Link extended selectio

Strany 9

E658130 - 16 - 5.4. Basic functions This clause shows the basic function of this CC-Link option using by CC-Link communication. 5.4.1. Run and fre

Strany 10 - E658130

E658130 - 17 - 5.5. I/O signal list 5.5.1. One station is occupied (CC-Link Ver.1) (c122=0) This option occupies one station area of the buffer me

Strany 11

E658130 - 18 - 5.5.2. Double setting is selected (CC-Link Ver.2) (c122=1) This option occupies one station area of the buffer memory of the PLC. In

Strany 12 - 4.5. LED indicator

E658130 - 1 - Introduction Thank you for purchasing the “CC-Link® option (CCL003Z)” for TOSVERT VF-S15 drive. This option can connect with open fiel

Strany 13 - 5. Functions

E658130 - 19 - 5.5.4. Octuple setting is selected (CC-Link Ver.2) (c122=3) This option occupies one station area of the buffer memory of the PLC. In

Strany 14

E658130 - 20 - 5.5.5. Trip history When “Quadruple setting” or “Octuple setting” of CC-LINK V.2 is selected, the past trip information can be refe

Strany 15 - 5.3.2. Baud rate setting

E658130 - 21 - 5.5.6. Detail of input and output signals 1. Output signals (Master -> Inverter) The output signals from the master unit are indic

Strany 16 - CC-Link extended selection

E658130 - 22 - Input function selection from the CC-Link. The function numbers selection of the RYn2 to RYn8 function valid from the command of the

Strany 17 - 5.4.2. Monitor

E658130 - 23 - 2. Input signal (Inverter -> Master) The following shows input signals to the master unit. (The output signals for the inverter.)

Strany 18 - 5.5. I/O signal list

E658130 - 24 - 5.5.7. Remote Register Assignment Divide the monitor code (RWw n) into half and select the monitor value 1 (RWr n) from the lower 8 b

Strany 19

E658130 - 25 - Address Signal Description RWwn+10 Instruction code 2 Set the command code for actions such as operation mode switching, paramet

Strany 20

E658130 - 26 - 2. Remote register (Inverter -> Master) RWr Address Signal Description RWr n Monitor value 1 When (RYnC) is on, the monitored

Strany 21 - 5.5.5. Trip history

E658130 - 27 - Address Signal Description RWrn+13 Read data 3 For a normal reply, the reply data to the instruction specified by the instructio

Strany 22 - to c148)

E658130 - 28 - 5.5.8. Instruction Codes Code No. Item Description 1003H Command mode selection read 2003H Command mode selection write 0: Ter

Strany 23

E658130 - 2 - Handling in general Warning Prohibited Do not connect or disconnect a network cable while the drive power is on. It may lead to

Strany 24 - : PI control prohibited

E658130 - 29 - Code No. Item Description 4900H to 6999H Read parameters (RAM) To read parameters a900 to c999, 6000H is subtracted from the param

Strany 25

E658130 - 30 - 5.5.9. The details of an error code The following data are stored as fault history data when the inverter trip occurred. Error code

Strany 26

E658130 - 31 - Error code Decimal No. Hexadecimal No. Description Trip display 50 32H Analog input break detection fault e-18 51 33H CPU communicat

Strany 27

E658130 - 32 - 5.5.10. Description of reply code When executing the frequency setting (RYnD) or instruction code execution (RYnF), check the reply

Strany 28

E658130 - 33 - 5.5.11. Description of monitor code Divide the monitor code (RWw n) into half and select the monitor value 1 (RWr n) from the lowe

Strany 29 - 5.5.8. Instruction Codes

E658130 - 34 - 5.5.12. Description of input terminal information Data composition of input terminal information (Code No. = 0FH). Bit Terminal na

Strany 30 -  A900H – 6000H = 4900H

E658130 - 35 - 6. Programming examples This chapter provides programming examples which control the inverter with the PLC. Item Programming Exam

Strany 31

E658130 - 36 - 2. Network parameter setting of the master station Network parameters are set as below.Item Setting Conditions Start I/O No. 0000 Da

Strany 32

E658130 - 37 - 3. The relation between the device of the programmable controller CPU and remote I/O (RX,RY) of the remote device station is as follo

Strany 33

E658130 - 38 - 6.1. Program example for reading the inverter status Example 1 shows a ladder logic to read the inverter status. Y30 of the output

Strany 34

E658130 - 3 - Table of Contents 1. OVERVIEW ...

Strany 35

E658130 - 39 - 6.2. Program example for setting the operation mode Example 2 shows a ladder logic to write data in the inverter. The operation mo

Strany 36 - 6. Programming examples

E658130 - 40 - 6.3. Program example for setting the operation commands Example 3 shows a ladder logic to give a forward command to station 2 invert

Strany 37

E658130 - 41 - 6.5. Program example for monitoring the output frequency Example 5 shows a ladder logic to read the output frequency of station 1 in

Strany 38

E658130 - 42 - 6.6. Program example for parameter writing Example 6 shows a ladder logic to chang the setting of f311 of station 1 inverter to 1 f3

Strany 39

E658130 - 43 - 6.7. Program example for parameter reading Example 7 shows a ladder logic to read parameter f311 of station 1 inverter to D2. f311:

Strany 40

E658130 - 44 - 6.8. Program example for trip information reading Example 8 shows a ladder logic to read the trip information of station 1 inverter

Strany 41

E658130 - 45 - 6.9. Program example for resetting the inverter at inverter error Example 9 shows a ladder logic to reset the station 2 inverter.

Strany 42

E658130 - 46 - 6.10. Instructions 1.Programming instructions 1.1 Since the buffer memory data of the master station is kept transferred (refreshe

Strany 43

E658130 - 47 - 7. Unusual diagnosis 7.1. Option error The error message is displayed when there is hardware error, software error or lose of co

Strany 44

E658130 - 48 - 7.3. How to check the error using the LEDs The following example explains the causes of fault which may be judged from the LED statu

Strany 45

E658130 - 4 - 1. Overview The option allows the VF-S15 drive to be connected into a CC-Link network. CC-Link supports a maximum of 42 nodes, allowin

Strany 46

E658130 - 49 - 2.When two or more inverters are connected The following example explains the causes and corrective actions for fault which may be j

Strany 47 - 6.10. Instructions

E658130 - 50 - 3. Communication stops during operation ▪ Check that the CC-Link units and the CC-Link dedicated cable are connected properly. (Che

Strany 48 - 7. Unusual diagnosis

E658130 - 5 - 2.1. CC-Link Version 2.1.1. CC-Link Ver. 1.10 The conventional CC-Link products, whose inter-station cable lengths have equally been

Strany 49 - Master

E658130 - 6 - 3. Names and functions The drawing below shows names and functions of main parts. 3.1. Outline LED indicator (See

Strany 50

E658130 - 7 - 4. Installation on inverter Refer to VF-S15 option adapter instruction manual (E6581838) for the installation on the inverter. Manda

Strany 51

E658130 - 8 - 4.3. Connection of CC-Link master unit and inverter The example of the connection of the CC-Link master unit and the inverter is show