DC injection braking wiil start when the inverter stop command is issued and the output frequency is less than
Time [S]
©When
©When
When
d bF
dbF
dbF
F - E n > reference frequency : DC injection braking is executed.
> reference frequency > F - E n Motor runs at the commanded frequency.
F - E n > reference frequency : DC injection braking is executed.
Note 1) The inverter stop command includes when the reference frequency becomes OHz, or when the
output frequency becomes less than F - En , in addition to the run/stop command.
© When a run command is issued during DC injection braking: DC injection braking is terminated, and the
motor starts running.
Time [S]
© During normal forward/reverse run (\ dbSL~|set to D), DC injection braking is not executed, as the
command is not regarded as an inverter stop command.
© When a reverse run (forward run) command is issued during a fonward run (reverse run); DC injection braking
starts when dbF > reference frequency during deceleration
When a run command is issued during DC injection braking; DC injection braking has priority.