1. System Configuration
Since there is no compatibility between the standard type and
the long-distance type, these two types cannot be mixed in one
T3 configuration.
The standard type expansion cable and the long-distance type
expansion cable are not compatible with each other. (See
Section 1.7 Expansion Cable.)
If the standard type is used, whether a power supply module is
necessary for the expansion unit will depend on the internal 5
Vdc current consumption. (See Section 1.9 Examining the
power supply capacity.)
For the IF351, change the power supply mode plug as shown in
the figure below (depending on whether a power supply module
has been mounted on its own unit).
IF351
Front
to 1-2 shorted (witii a power supply).
For the long-distance type, a power supply module is needed for
each of the expansion units.
In the long-distance type, the IF312 is for basic unit, the IF352 is
for middle expansion units and the IF353 is for the end
expansion unit.
1.7
Expansion cable
The following types of expansion cables are available.
Type
Cable length Remarks
1
CS3R5
0.5m
Standard type
With both-end connectors (50-pin)
2
CS301
1m
3
CS302 2m
4
CL3R5 0.5m
Long-distance type
With both-end connectors (68-pin)
.5
GL301 1m
6
CL305
5m
7
CL310
10m
8
CL320 20m
9
CL340 40m
User’s manual - Hardware
21